Không có sản phẩm nào trong giỏ hàng của bạn
Không có sản phẩm nào trong giỏ hàng của bạn
*The Module DSE704 has been designed to monitor engine temperature, low oil pressure fail to start,
charge failure, over speed and under speed.
*Automatic mains (utility) supply monitoring
*Automatic shutdown when fault conditions are detected
*Manual start
*Engine pre-heat
*Engine monitoring and protection features
*Protected solid state (PSS) outputs
*Front panel mounting
*Front panel programming
*Remote start
*LED indicators
*Configurable timers
*Configurable outputs
*ransfers between mains (utility) and generator power
* On-site module configuration to match user requirements
* Multiple engine parameters are monitored simultaneously
DC Supply: |
8 Volts to 35 Volts DC Continuous. |
Cranking dropouts: |
Able to survive 0 Volts for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 Volts. This is achieved without the need for internal batteries. |
Max. Current: |
Operating 50mA |
Standby 10mA |
|
alternator Input Range: |
75 Volts (ph-N) to 277 Volts (ph-N) AC (+20%) |
Mains Input Voltage: |
15 – 277 Volts (ph-N) AC (+20%) |
alternator Input Frequency: |
50 - 60 Hz at rated engine speed (Minimum: 75V AC Ph-N) (Crank Disconnect from 15V Ph-N @ 20Hz) |
Overspeed +14% (+24% overshoot) |
|
Underspeed –20% |
|
Mains Frequency: |
50 – 60 Hz |
Start Output: |
1.2 Amp DC at supply voltage. |
Fuel Output: |
1.2 Amp DC at supply voltage. |
Auxiliary Outputs: |
1.2 Amp DC at supply voltage. |
Dimensions: |
125mm x 165mm x 28 mm |
Charge Fail: |
12 Volts = 8 Volts CF 24 Volts = 16 Volts CF |
Operating Temperature Range: |
-30°C to + 700C |
Applicable Standards: |
Compliant with BS EN 60950 Low Voltage Directive |
Compliant with BS EN 50081-2: 1992 EMC Directive |
|
Compliant with BS EN 61000-6-4: 2000 EMC Directive |
Starting Controller Series ---------