*The Model 5120 is an Automatic Mains Failure Module which has been designed to allow the OEM to meet demand
for increased capability within the generator industry.
*The module has been primarily designed to monitor the incoming mains supply.
*Should the mains supply fall below a configurable limit, the generator will be automatically started and the load
transferred.
*When the AC mains supply returns to within limits, the module will then transfer back to the mains.
*The module indicates the operational status of the generator and monitors the engine parameters.
*Should a fault condition occur, the module will shut down the engine indicating any faults by means of a graphical LCD
display and a flashing LED on the front panel.
*selected operational timers and alarms can be adjusted by the customer.
*Micro-processor based design.Integral mains failure monitoring and load switching control.
*Automatic engine starting and stopping.
*Automatic shutdown on fault condition.
*Custom graphical icon display.
*Provides engine and generator instrumentation.
*Provides engine alarms and status information.
*Comprehensive list of timers and pre-configured sequences.
*Front panel and PC configurable inputs, outputs,alarms and timers.
*LED and LCD alarm indication.
*Compatible with 5200 series modules for easy upgrade path.
Power Supply | 8 to 35 Vdc Continuous |
Cranking dropouts: | Able to survive 0 V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V without the need for internal batteries. |
Max Current | Operating 320mA at 12V, 215mA at 24V; Standby 175mA at 12V, 95mA at 24V |
Start Relay Output: | 16 Amp DC at supply voltage. |
Fuel Relay Output: | 16 Amp DC at supply voltage. |
Auxiliary Relay Outputs: | 5 Amp DC at supply voltage. |
Charge Fail / Excitation Range | 0 V to 35 V |
alternator Input Range: | 15V(ph-N) to 300V(ph-N) 3 Phase 4wire AC (+20%) |
alternator Input Frequency: | 50 - 60 Hz at rated engine speed (Minimum: 15V AC Ph-N) |
Mains Supply Input Range: | 15V(ph-N) to 300(ph-N) 3 Phase 4wire AC (+20%) |
Mains Supply Input Frequency: | 50 - 60 Hz at rated engine speed (Minimum: 15V AC Ph-N) |
Magnetic Pick-up Voltage Input Range: | +/- 0.5 V to 70 V Peak |
Magnetic Input Frequency: | 10,000 Hz (max) at rated engine speed |
Operating Temperature Range: | -30 to +70°C |
Panel Cutout: | 220mm x 160mm ( 8.7” x 6.3” |
RelativeItem NO. |
DSE501K | DSE701AS | DSE701MS | DSE702AS | DSE702 MS | DSE704 |
Relative Item NO. | DSE5210 | DSE5120 | DSE5110 | DSE720 | DSE710 |